Initial installation, Qualified installers only – Enviro Haven Direct Vent Fireplace User Manual

Page 14

background image

Initial Installation

QUALIFIED INSTALLERS ONLY

The framing boards may touch the top, side and back standoffs, but no insulation or other material

can be placed between the frame and the standoffs.
The gas line, 3⁄8 inch NPT, can be brought to either the right side, the left side, or the bottom of

the fireplace. If this set up is inconvenient, the electrical wire and the gas line configuration can be

reversed.
The location should be chosen so the fireplace must be at least 36 inches (91.4 cm) from drapes, doors

and other combustibles. The framed opening should also be a minimum of 3.5 inches (8.9 cm) from the

nearest perpendicular wall (sidewall to the edge of the opening).

The HAVEN is designed so it can be installed at floor level without a required hearth

.

C

ORNER

I

NSTALLATION

:

R

AISED

F

IREPLACES

AND

H

EARTHS

:

Even though the Haven can be installed at floor level without a hearth, there are a few options with raised

fireplaces: raised with a floor level hearth (Figure 17), raised with a raised hearth (Figure 18), or raised

with no hearth (Figure 19). If the fireplace is raised, it cannot be placed within 18 inches (45.7cm) of the

ceiling. When installing a raised fireplace, it is imperative that the support stand is strong enough to hold

the weight of the fireplace (up to 140lb [63.5Kg]) and venting.

Figure 16. Dimensions for a corner installation.

2" x 6"

Stud

1

/

2

" (13mm)

Front Facing

18

15

/

16

"

(481mm)

30

5

/

16

"

(770mm)

21

7

/

16

"

(545mm)

6

3

/

8

"

(162mm)

The dimensions for installing a

fireplace in the corner of a room

are given in Figures 16. Refer

to “I

NITIAL

I

NSTALLATION

- V

ENT

C

ONFIGURATIONS

AND

R

ESTRICTOR

S

ETTINGS

” for allowable pipe

lengths.
Do not interfere with the

structural integrity of the walls.

14