Specifications, Scc 2120 and tac 2110, Appendix a – Verilink APS 2000 T1 Line Protection (880-502411-001) Product Manual User Manual
Page 79: Appendix

Verilink APS 2000 User Manual
-1
Appendix
A
Specifications
SCC 2120 and TAC 2110
Interfaces
DS-1 Equipment
Network
Line Rate
1.544 Mbps
±
32 ppm
1.544 Mbps
±
32 ppm
Line Code
AMI, B8ZS
AMI, B8ZS
Framing Formats
Unframed, SF, ESF
Unframed, SF, ESF
Impedance
100 ohms
±
5%
100 ohms
±
5%
Input Level
3.0 V
±
0.3 V base-to-peak, attenuated by
up to 655 feet of cabling
DS-1 attenuated by 0 to 27.5 dB
Pulse Width
324
±
45 nanoseconds at half amplitude
324
±
45 nanoseconds at half amplitude
Pulse Afterkick
10% to 30% of pulse peak
10% to 30% of pulse peak
Output Level
DSX-1 into 100 Ohms
3.0 V
±
0.3 V base-to-peak
Output LBO
N/A
0, 7.5, or 15 dB (0 to 3000 feet), selectable
Pulse Density
Enforcement
N/A
12.5% average density and 80 zeros, AT&T
62411, 15 zeros, 80 zeros, or none
Pre-equalization
0 to 655 feet, selectable
N/A
Surge Protection
Up to 400 Vp-p
Up to 400 Vp-p
Loopbacks
Equipment (ELB
Controlled via ESF Data Link
Repeater (RLB)
Controlled via ESF Data Link
Line (LLB)
Controlled via in-band codes, or TABS or ANSI
T1.403 commands on the ESF Data Link
Payload (PLB)
Controlled via TABS or ANSI T1.403 commands on
the ESF Data Link
All loopbacks are accessible via the ASCII terminal.
Alarm rela
Contacts Provided
Normally open, normally closed and common lead
Configuration
Form C
Contact Rating
1A at 52 V
dc
or 2A at 26 V
dc
, non-inductive
Closure Conditions
SCC/CSU hardware failure
LOS from network or DS-1 equipment
Loss of synchronization from network
Loss of synchronization from equipment
Loopback in progress
Loss of power
Removal of CSU from shelf
LOF
Excessive BER
Excessive BPV (>10
-4
)