ELECTRICAL SAFETY TESTER

USER MANUAL



33

z Continuous AC/DC withstanding voltage test (CAC,CDC-only

for GPT-715A/GPI-735A/745A)
The CAC/CDC test is available only on step “0:0”. Like the
traditional hi-pot tester, you can use the knob and arrow keys to
adjust output voltage during test.
All the parameters of CAC/CDC are the same as ACW/DCW, except
the testing time. The testing of CAC/CDC is not limited.

z Insulation Resistance test (IR- only for GPI-725A/735A/745A)

Press MENU key to enter status MENU then use knob and arrow
keys to select a step.
Press EDIT/SAVE key to enter status EDIT. Now the cursor stays at
the “test mode” field. Use the knob to select mode IR.
Functionality of FIELD key:

Test mode

IR

Output voltage

V=X.XXXkV

Measurement upper limit

Rmax=XXXXMΩ

Measurement lower limit

Rmin=XXXXMΩ

Testing time

TEST=XXX.Xs

Channel

Hi=00

Lo=00


ELECTRICAL SAFETY TESTER

USER MANUAL



34

Press FIELD key to edit next field “output voltage”. Use the knob to

adjust the desired output voltage (50V/100V/500V/1000V).

Press FIELD key again to enter next field “measurement upper

limit”. Use the knob to adjust the desired upper limit of resistance
while use the arrow keys to adjust the knob’s resolution(0~9999MΩ,

0~2000MΩ 50V/100V).

Press FIELD key again to enter next field “measurement lower

limit”. Use the knob to adjust the desired lower limit of resistance
while use the arrow keys to adjust the knob’s resolution(0~9999MΩ,

0~2000MΩ 50V/100V).

Press FIELD key again to enter next field “testing time”. Use the

knob to adjust the desired testing time while use the arrow keys to

adjust the knob’s resolution (1.0~999.9s).

Press FIELD key again to return the first field “test mode” again.

Press EDIT/SAVE key to save all the parameters.