Chapter 6 specifications – Seaward Europa Pac Plus User Manual
Page 48

AC Earth Continuity Test
42
Chapter 6 Specifications
AC Earth Continuity Test
Test Voltage *.. ............................................6V rms nominal (no load)
Test Current *......................................................... 10A (into s/c load)
Range............................................................................. 0m
Ω - 19.99Ω
Resolution. ................................................................................. .0.01
Ω
Accuracy..................+/- 5% of reading, +/- 2 digits (0.05 - 5.00 ohms)
Pass Levels. ........................................................... 0.1
Ω, User defined
Misc.............................................. ..4-wire measurement, floating earth
DC Earth Continuity Test
Test Voltage *. ...............................................4V dc nominal (no load)
Test Current * .....................................+200mA, -200mA (into s/c load)
Range ......................................................................... .00m
Ω - 19.99Ω
Resolution. ................................................................................ ..0.01
Ω
Accuracy..................+/- 5% of reading, +/- 2 digits (0.05 - 5.00 ohms)
Pass Levels. ............................................................0.1
Ω, User defined
Misc............................................... .4-wire measurement, floating earth
Insulation Test
Test Voltage * .............. 500V d.c. or 250V d.c. nominal (0.5M
Ω load)
Short Circuit Current ............................................ 2mA d.c. maximum
Range............................................................................ 00k
Ω - 100 MΩ
Resolution .............................................................0.01 M
Ω (<100 MΩ)
Accuracy...................... .+/- 5% of reading, +/- 2 digits (100k
Ω - 5MΩ)
Pass Levels….. ..….0.25M
Ω, 0.50MΩ, 1.0MΩ, 2.0MΩ, User defined