Remote Condenser Location

Use the following for planning the placement of

the condenser relative to the ice machine

Location Limits - condenser location must not

exceed ANY of the following limits:

·

Maximum rise from the ice machine to the

condenser is 35 physical feet

·

Maximum drop from the ice machine to the

condenser is 15 physical feet

·

Physical line set maximum length is 100 feet.

·

Calculated line set length maximum is 150.

Calculation Formula:

·

Drop = dd x 6.6 (dd = distance in feet)

·

Rise = rd x 1.7 (rd = distance in feet)

·

Horizontal Run = hd x 1 (hd = distance in feet)

·

Calculation: Drop(s) + Rise(s) + Horizontal Run

= dd+rd+hd = Calculated Line Length

Configurations that do NOT meet these

requirements must receive prior written

authorization from Scotsman.

Do NOT:

·

Route a line set that rises, then falls, then rises.

·

Route a line set that falls, then rises, then falls.

Calculation Example 1:

The condenser is to be located 5 feet below the ice

machine and then 20 feet away horizontally.

5 feet x 6.6 = 33. 33 + 20 = 53. This location would

be acceptable

Calculation Example 2:

The condenser is to be located 35 feet above and

then 100 feet away horizontally.

35 x 1.7 = 59.5. 59.5 +100 = 159.5. 159.5 is

greater than the 150 maximum and is NOT

acceptable.

NME654R & FME804R

January 2000

Page 5

22.87"

17.15"

40.35"

hd

rd

dd

Remote

Condenser

Located ABOVE

Ice Machine

Remote

Condenser

Located BELOW

Ice Machine

Condenser Distance and

Location Schematic