NME654R & FME804R

January 2000

Page 26

SERVICE DIAGNOSIS:

Symptom

Possible Cause

Probable Correction

No ice is made, nothing operates

Unit off due to no power.

Restore power

Unit off due to master switch in Off

position

Move master switch to ON

Unit off due to low water level in

reservoir

Check water supply, filter and float

valve.

Unit off due to ice level sensors

(photo-electric eyes) blocked

Check/clean ice level sensors

Unit off due to scale on water level

sensor

Clean water level sensor

Unit off due to high pressure control

open

Check for remote condenser fan

motor failure or power interuption to

the fan motor

Auger motor hums but does not turn Auger can’t turn. Circuit board has not

yet shut unit down.

Unit is shut down

Circuit board has shut ice machine

down due to high auger motor amp

draw. Check for cause of high amp

draw, including bearings, gear motor

condition and scale on auger &

evaporator.

Pump down pressure control open,

very low suction pressure

Auger not turning due to: motor

failure; auger relay failure on circuit

board; or gears stripped. Check drive

train.
Liquid line valve not opening due to

coil failure or failure of compressor

relay on circuit board
TXV restricted or not metering. Check

bulb temperature.
Lack of refrigerant. Check for a leak.

No power to circuit board

Check harness
Hi or Low pressure switch open

Circuit board gear motor relay will not

close

Check / replace board

Water level or ice level sensor failed Check / replace sensor