CHARGING

CYLINDER or

SCALE

RECEIVER

SERVICE PORT

REFRIGERATION SERVICE

General Information:

Work on the refrigeration system should only be

done when it is certain that the system needs

repair.

·

Refrain from checking refrigeration

pressures without reason. Visual inspection

of the water system, observation of the ice

formation, amp draw, voltage, and other

techniques will lead to proper diagnosis.

Scotsman also recommends that, at the time of

initial start up, gauges not be used.

·

If gauges must be used, don’t always check the

high side pressure. If the condenser is clean

and seems to be operating correctly, it most

likely is. The low side pressure is more

important on an ice machine than the high side.

·

If gauges must be used, use very short hoses to

minimize refrigerant discharged into the air.

·

Refrigerant should not be added except as a

way to determine the proper operation of the

product. If the system was low on refrigerant,

there is a leak, and it must be found and

repaired.

·

This system has a critical charge, it must be

recharged with the correct amount of refrigerant

as listed on the nameplate of the ice machine,

or performance will suffer.

·

Anytime the refrigeration system has been

opened, the dryer should be replaced. Note:

Only a HFC type dryer should be used.

·

When brazing the tubing connections to

components such as the TXV, the component

must be protected by heat sink material.

·

When brazing a nitrogen purge is required.

·

Evacuate to 300 microns.

Recover, reclaim or recycle refrigerant.

Access Valves: To use the access valves:

Remove the cap from the stem, use a 3/16" allen

wrench to check that the valve is CLOSED. The

remove the core cap.

Torque Stem Cap

to 8-12 ft. lb.

Torque Stem to

Torque Core

Cap to 7-12

ft. lb.

Access Valves

Note: There are no valve

cores in this valve.

Allen

Wrench

Charging Procedures

Extra care must be taken when recharging this

remote system. No liquid refrigerant may be placed

in the system at the compressor.

DO NOT use the valves at the front of the unit for

weighing in the charge. All liquid HP62 must be

weighed into the receiver through the “front seated”

king valve".

FRONT SEATED

KING VALVE