SERVICE DIAGNOSIS

Symptom

Possible Cause

Probable Correction

No ice is made, nothing

operates

Unit off due to no power.

Restore power

Unit off due to master switch in Off position Move master switch to ON
Unit off due to low water level in reservoir

Check water supply, filter and

float valve.

Unit off due to ice level sensors

(photo-electric eyes) blocked

Check/clean ice level sensors

Unit off due to scale on water level sensor

Clean water level sensor

Auger motor hums but does not turn

Auger can’t turn. Circuit board

has not yet shut unit down.

Auger turning but there is no refrigeration

effect

Liquid line valve not opening,

check coil, check board relay.
No refrigerant to ice machine,

check main system.

Unit is shut down

Circuit board has shut ice

machine down due to high auger

motor amp draw. Check for

cause of high amp draw,

including bearings, gear motor

condition and scale on auger &

evaporator. May also be due to

liquid line valve leak thru during

the off cycle. Check valve.

Auger not turning

Due to: motor failure; auger relay

failure on circuit board; or gears

stripped. Check drive train.

Low suction pressure

Liquid line valve not opening due

to coil failure or failure of

compressor relay on circuit board
EPR setting too low, check/adjust
TXV restricted or not metering.

Check bulb temperature.

No power to circuit board

Check harness

Circuit board gear motor relay will not close Check / replace board
Water level or ice level sensor failed

Check / replace sensor

No ice, auger motor is

turning

Liquid line valve coil is open

Check / replace valve coil

Circuit board relay will not close

Check / replace board

Unit makes ice, but very

slowly

High discharge pressure because of dirty

condenser

Clean condenser.

Auger and evaporator are coated with

minerals

Clean the water system

Low suction pressure due to low EPR

setting

Adjust EPR, check TXV

superheat

Double System RL

November 2000

Page 18