OPERATION: Refrigeration

The remote high side supplies high pressure liquid

refrigerant to the liquid line connection on the ice

machine. After the sight glass, there are two

separate liquid lines, each leading to a liquid line

valve. When the individual ice level sensor causes

the circuit board to energize the liquid line valve,

the valve opens, allowing the liquid refrigerant to

enter that expansion valve. The thermostatic

expansion valve meters the liquid refrigerant into

the evaporator, where it

boils off (evaporates) and

absorbs heat. It then

moves through the ball

valve and into the

evaporator pressure

regulator valve, or EPR.

The EPR keeps the

evaporator pressure

above a predetermined

point, even though the

suction line pressure of

the remote high side

system may vary. The

refrigerant, now a low

pressure gas, moves into

the suction line of the

remote high side system.

Double System RL

November 2000

Page 13

LIQUID

LINE

SIGHT GLASS

HAND VALVE

LIQUID LINE

VALVE

THERMO VALVE

EVAPORATORS

BALL VALVES

EPR VALVE

SUCTION LINE