ELECTRICAL SEQUENCE

There are 7 indicator lights on the control board:

·

WTR-OK (Water OK).

Green.

Normal =

Glowing. Glows when there is water in the

reservoir.

·

PWR-OK (Power OK).

Green.

Normal =

Glowing. Glows when the control board has

power and is functional.

·

Service.

Red.

Normally Off.

·

Freeze.

Red.

Normally glowing when making

ice.

·

Bin Full.

Red.

Normally Off when making ice.

·

LED1. White. Located next to the board’s

Compressor Relay (used to power the liquid line

valve). Normally Glowing when making ice.

·

LED3. White. Located next to the board’s Auger

Motor Relay. Normally Glowing when making

ice.

If the machine is switched off at the mode switch,

but is otherwise ready to go, switching the mode

switch to ON does the following:

·

The PWR-OK light glows.

·

If there is water in the reservoir the WTR-OK

light glows.

·

After 10 seconds the Freeze, LED1 and LED3

lights glow and the machine starts up.

Start Up:

·

The compressor relay and auger motor relay

become energized, connecting power to the

windings of the auger motor and liquid line valve

coil.

·

The liquid line valve opens, refrigerant flows to

the expansion valve and ice making begins.

·

As ice is made it passes between the ice level

sensors but because it is not a continuous

stream it only interrupts the sensor’s infrared

beam momentarily. The bin full light remains off

and the machine stays on until ice builds up in

the bin and blocks the path between the

sensors for 6 seconds or longer. When that

occurs the bin full light glows and the machine

shuts down.

Shut Down:

·

The compressor relay opens, LED1 goes out.

·

The liquid line valve closes.

·

The refrigerant flow stops.

·

The auger motor stays on for 1 more minute,

clearing out ice in the evaporator, and then

·

The auger motor relay opens, LED3 goes out

and the auger motor stops.

The liquid line valve will not re-open until 2 minutes

or more have passed after the last shut down.

If the path between the ice level sensors remains

clear for more than 10 seconds the ice machine

will restart.

Control Board Protection Devices

·

When the water level in the reservoir falls

below the water level sensor’s tip, the WTR-OK

light goes out and the machine shuts down.

When water refills the reservoir the WTR-OK

light glows and the machine starts up again.

·

If the auger drive motor current becomes

excessive the compressor and auger drive

motor will be switched Off and the Service light

will blink. The control board will restart the auger

drive motor in 4 minutes. If during the first 60

seconds after restart the auger motor current

stays within limits, the liquid line valve is

reopened and the machine returns to normal

operation. If the auger motor’s current is

excessive within 60 seconds after the restart,

the process will be repeated once more. If

during that try the current is still excessive the

machine shuts down and must be manually

reset. The service light will then be glowing

continuously.

To Reset: Disconnect and reconnect electrical

power to the unit.

The mode (on - off) switch is the manual control

for the complete machine, but it is not a service

disconnect.