Remotec ZTS-110 V3.14 User Manual

Page 36

background image

36

Upper limit of heat set point 

 

(Advance user can limit the 

upper heat set point in order to 

have energy saving) 

6 (0x06) 

Unit in C:   

Range from 5

o

C to [(37

o

C) ‐ (dead band)] 

Range from 50 (0x0032) to 355 (0x0163) 

Example 28

o

C; input = 280 (0x0118) 

Unit in F:   

Range from 41

o

F to [(99

o

F) ‐ (dead band)] 

Range from 410 (0x019A) to 960 (0x03C0) 

Example 82

o

F; input = 820 (0x0334) 

Default = (99

o

F) ‐ (dead band) 

Lower limit of cool set point 

 

(Advance user can limit the 

lower cool set point in order to 

have energy saving) 

7 (0x07) 

Unit in C:   

Range from [(5

o

C) + (dead band)] to 37

o

Range from 65 (0x0041) to 370 (0x0172) 

Example 20

o

C; input = 200 (0x00C8) 

Unit in F:   

Range from [(41

o

F) + (dead band)] to 99

o

Range from 440 (0x01B8) to 990 (0x03DE) 

Example 68

o

F; input = 680 (0x02A8) 

Default = (41

o

F) + (dead band) 

Easy Mode 

8 (0x08) 

0 (0x00) = Disable   

1 (0x01) = Enable, default 

Time format 

9 (0x09) 

0 (0x00) = 24 hours 

1 (0x01) = 12 hours (am / pm), default 

Repeat basic set counter 

(Association Group A and B 

only) 

10 (0x0A) 

Value(X) 

0 (0x00), 3 (0x03) to 255 (0xFF) 

0 (0X00) = Disable, default 

3 (0x03) to 255 (0xFF) minutes     

(Thermostat sends “Basic Set” command to 

its association node repeatedly in every X 

minutes) 

Trigger AUTO report if room 

temperature is different from 

last report. 

(It will report room 

temperature only) 

 

*User can use this function to 

enhance batteries service life. 

11 (0x0B) 

0 (0x00) = disable AUTO report if room 

temperature is different from last report. 

 

AUTO report if room temperature is 

different from last report. 

Delta change is >= 

1 (0x01) = 1

o

F (0.5

o

C) 

2 (0x02) = 2

o

F (1.0

o

C) 

3 (0x03) = 3

o

F (1.5

o

C) 

4 (0x04) = 4

o

F (2.0

o

C), default 

5 (0x05) = 5

o

F (2.5

o

C)