Remotec ZTS-110 V3.14 User Manual
Page 36

36
Upper limit of heat set point
(Advance user can limit the
upper heat set point in order to
have energy saving)
6 (0x06)
Unit in C:
Range from 5
o
C to [(37
o
C) ‐ (dead band)]
Range from 50 (0x0032) to 355 (0x0163)
Example 28
o
C; input = 280 (0x0118)
Unit in F:
Range from 41
o
F to [(99
o
F) ‐ (dead band)]
Range from 410 (0x019A) to 960 (0x03C0)
Example 82
o
F; input = 820 (0x0334)
Default = (99
o
F) ‐ (dead band)
Lower limit of cool set point
(Advance user can limit the
lower cool set point in order to
have energy saving)
7 (0x07)
Unit in C:
Range from [(5
o
C) + (dead band)] to 37
o
C
Range from 65 (0x0041) to 370 (0x0172)
Example 20
o
C; input = 200 (0x00C8)
Unit in F:
Range from [(41
o
F) + (dead band)] to 99
o
F
Range from 440 (0x01B8) to 990 (0x03DE)
Example 68
o
F; input = 680 (0x02A8)
Default = (41
o
F) + (dead band)
Easy Mode
8 (0x08)
0 (0x00) = Disable
1 (0x01) = Enable, default
Time format
9 (0x09)
0 (0x00) = 24 hours
1 (0x01) = 12 hours (am / pm), default
Repeat basic set counter
(Association Group A and B
only)
10 (0x0A)
Value(X)
0 (0x00), 3 (0x03) to 255 (0xFF)
0 (0X00) = Disable, default
3 (0x03) to 255 (0xFF) minutes
(Thermostat sends “Basic Set” command to
its association node repeatedly in every X
minutes)
Trigger AUTO report if room
temperature is different from
last report.
(It will report room
temperature only)
*User can use this function to
enhance batteries service life.
11 (0x0B)
0 (0x00) = disable AUTO report if room
temperature is different from last report.
AUTO report if room temperature is
different from last report.
Delta change is >=
1 (0x01) = 1
o
F (0.5
o
C)
2 (0x02) = 2
o
F (1.0
o
C)
3 (0x03) = 3
o
F (1.5
o
C)
4 (0x04) = 4
o
F (2.0
o
C), default
5 (0x05) = 5
o
F (2.5
o
C)