Support for association groups – Remotec ZTS-110 V3.14 User Manual
Page 33

33
4
Press “Home" key once to go
back to the home page.
will disappear on the main
display
Support for Association Groups
ZTS‐110 supports 3 association groups.
Association group_1
(Heat pump)
Association group_2
(Compressor)
Association group_3
(Auto Report)
Heating mode
ON
(basic set command 0xFF)
OFF
(basic set command 0x00)
‐
Cooling mode
OFF
(basic set command 0x00)
ON
(basic set command 0xFF)
‐
OFF
OFF
(basic set command 0x00)
OFF
(basic set command 0x00)
‐
Association group_3: (Auto report)
z
Association group_3 is used to report status change to gateway.
(Only gateway or controller can be assigned in this association group)
ZTS‐110 will trigger AUTO report function if one of below status is changed.
I.
Operation mode (Off, Heat, Cool, Auto)
II.
Operation state (Heat on or off, Cool on or off)
III.
Fan mode (Auto, Auto low)
IV.
Fan state (Fan on or Fan off)
V.
Heat set point (report in precision 1 after decimal, e.g. 21.1
o
C )
VI.
Cool set point (report in precision 1 after decimal, e.g. 23.3
o
C )
VII. Current room temperature (report in precision 1 after decimal, e.g. 24.0
o
C)
(It will trigger room temperature report if there is 4
o
F or 2
o
C (default) differ from last report.
You can change this setting by set the configuration parameter)
Note:
Total 5 devices (nodes) can be assigned in total 3 association groups. Below table lists out the devices
(nodes) allocations in the 3 association groups.
Case no.
No. of Node ID in
Association Group_1
No. of Node ID in
Association Group_2
No. of Node ID in
Association Group_3
Case 1
4
0
1 (AUTO report)
Mode
Association group