Set temperature of the storage tank during
solar charging
Once the solar set temperature is reached, the
solar cycle pump is switched off. With the collector
cooling function activated, the temperature of the
storage tank can continue to rise as far as the set
maximum temperature.
The solar set temperature (select with the rotary
knob and confirm with "OK") should be reduced if
the hot water temperature is regularly too high or if
there is no thermostatic mixing valve installed. At
the same time, when the collector cooling function
is activated, the max. temperature of the storage
tank must be reduced.
Fig. 65: Set temperature of the storage tank
Menu item
Parameter
Factory setting
Solar set
temperature
5°C - 95°C
85°C
Press "Next".
Solar heating
If heating is to be provided from the available solar
yield (if required), this parameter must be acti-
vated.
If another heat generator is connected to the
system hydraulically, e.g. water-based chimney
heat exchanger, this parameter must be activated.
Fig. 66: Solar heating
Menu item
Parameter
Factory setting
Solar
heating
Deactivated
Deactivated
Activated
REMKO recommends installing a domestic hot
water mixer.
Once the last parameter has been entered into the
commissioning wizard, the screen switches to the
overview mode (3D house).
37