REMKO WPM-Smart-Control-Manual for specialists-WKF-085 User Manual
Page 33

Building
type
Heat retention ability
Recom-
mended value
Light
Low heat retention ability, e.g. prefab / wood-frame houses
approx. 10h
Medium
Moderate heat retention ability, e.g. house made from hollow blocks
approx. 20h
Heavy
High heat retention ability, e.g. brick house
approx. 30h
Very heavy
Very high heat retention ability, e.g. exterior and interior walls > 30cm
approx. 60h
Passive
Well-insulated, e.g. zero-energy housing
approx. 100h
Fig. 55: Setting the building time constant
Menu item
Parameter
Factory setting
Building time
constant
0 - 100 h
According to
design! - 10 h
Press "Next".
Setting the standard heating load
Set the standard heating load (select with the
rotary knob and confirm with "OK"). The standard
heating load is obtained by multiplying the specific
heating load by the living area to be heated. You
can calculate the standard heating load from the
following table.
Building performance requirements
Year of construction
Specific heating load
Up to 1970, uninsulated
120 - 180 W/m
2
1977 to 1984
70 - 100 W/m
2
1985 to 1995
50 - 70 W/m
2
New build, EnEv
40 - 50 W/m
2
New build, KfW 40/60
20 - 30 W/m
2
Zero-energy house
10 - W/m
2
Fig. 56: Setting the standard heating load
Menu item
Parameter
Factory setting
Standard
heating load
0 - 25 kW
According to
design! - 14.0
kW
Press "Next".
33