REMKO WPM-Smart-Control-Manual for specialists-WKF-085 User Manual
Page 31

System separation
Activation if the floor heating cycle is separated by
a heat exchanger.
To control a separate heating cycle pump with a
system separation by means of a heat exchanger,
the function System separation FBHmust be acti-
vated (select with the rotary knob and confirm with
"OK").
Fig. 50: Activating the system separation
Menu item
Parameter
Factory setting
System sep-
aration FBH
Deactivated
Deactivated
Activated
For optimal configuration of the heating curve
parameters, the heating load calculation and/or
energy consumption must be taken into account.
Differences between the installed parameters and
the design of the actual building can cause the
heat pump to run inefficiently.
Operating the heating cycle with a fixed value is
not recommended, as it will cause the heat pump
to operate inefficiently.
Heating cycle for radiator heating
Activate if a heating cycle with radiators is
installed. (select with the rotary knob and confirm
with "OK")
Fig. 51: Activating the heating cycle for radiator
heating
Menu item
Parameter
Factory setting
Heating
cycle for
radiator
heating (HK)
Deactivated
Deactivated
Activated
Press "Next".
Setting heating cycle mode
This is where you can select between the different
heating cycle modes. The choice is between con-
trol according to the set "Heating curve" and
"Fixed value control" (select with the rotary knob
and confirm with "OK").
Menu item
Parameter
Factory setting
Heating
cycle mode
for HK active
Heating curve
According to
design
Fixed value
10°C - 40°C
Press "Next".
Heating-curve heating cycle mode
The heating curve can be adjusted in three points,
according to the structure and location-related con-
ditions of the building:
Base point:
The base point corresponds to the minimum set
temperature of the heating water at an outside
temperature of 20°C. If the heating is too cold at
relatively high outside temperatures (trans-sea-
sonal period), the base point should be set higher.
31