Remko smart wp manager – REMKO WPM-Smart-Control-Manual for specialists-WKF-085 User Manual
Page 30

Heating-curve heating cycle mode
The heating curve can be adjusted in three points,
according to the structure and location-related con-
ditions of the building:
Base point:
The base point corresponds to the minimum set
temperature of the heating water at an outside
temperature of 20°C. If the heating is too cold at
relatively high outside temperatures (trans-sea-
sonal period), the base point should be set higher.
Standard inlet temperature:
the standard inlet temperature corresponds to the
set temperature of the heating water at the
standard outside temperature in the building loca-
tion. If the heating is not warm enough at low out-
side temperatures, the standard inlet temperature
should be increased.
Standard outside temperature:
the standard outside temperature is dependent on
the regional location of the building. Please consult
your heating installer.
2
1
4
3
Fig. 46: Heating curve adjustment
1: Temperature of the heating water in °C
2: Inlet temperature heating curve
3: Return flow heating curve
4: Outside temperature in °C
Setting the heating curve:
- Activate the base point with the right softkey, set
with the rotary knob and conform with the right
softkey.
Fig. 47: Setting the base point
- The standard inlet temperature and the outside
temperature are set using the same procedure.
Fig. 48: Setting the standard inlet temperature
Fig. 49: Setting the outside temperature
Fixed-value-control heating cycle mode
Specify the set temperature for fixed value control
(select with the rotary knob and confirm with "OK").
The heating cycle is kept permanently at this tem-
perature in fixed value control.
Press "Next".
REMKO Smart WP MANAGER
30