Fault

description

Cause

Remedy

Module over-

temperature

The air supply to

the module

cooling element

is restricted

The motor is switched off if an overtemperature situation occurs. A

restart occurs after 30 seconds. After the motor has been switched off

for the fifth time, it is switched off permanently. This can only be reset by

switching the power off for more than 30 seconds. The SSM relay is

active as long as the internal error counter is not ZERO.

Cable break

Control is defec-

tive, control line

is defective

A cable break is registered for the pumps that are controlled via a 0-10 V

signal and that are equipped with software with a cable break function if

the inbound control signal is less than 0.5 V. The pump turns at min-

imum speed.