2.4

Pump unit data

Technical data

Pump group

HGM / HGU

Pump type

Wilo Stratos Para 25 / 1-7 T1

Maximum delivery volume

m

3

4.5

Maximum delivery height

m

7.0

Speed

rpm

1200 - 4450

Mains voltage

1~230V

± 10% in accordance with DIN IEC 60038

Energy Efficiency Index ( EEI )

£ 0.23

Frequency

Hz

50/60 Hz

Insulation class

F

Enclosure class

IP 44

Rated input P1

W

5 - 70

Nominal width for pipe connection Rp

Inch

es

1"

Connection flange thread G

Inch

es

1 1/2"

Permitted ambient temperature

°C

+ 40

Maximum relative humidity

£ 95%

Permitted conveying media

Heating water (in accordance with VDI 2035/VdTÜV

Tch 1466)

Water/Glycol mixture: maximum mixture ratio is 1:1 (in

mixtures with Glycol, the delivery data of the pump

must be corrected according to the higher viscosity and

depending on the mixture ratio percentage.)

Ethylene/propylene glycol with corrosion protection

inhibitors

- Standard oxygen binding agent

- Standard corrosion protection agent

- Standard combination products

- Standard cooling brines

Permitted medium temperature

°C

95

Maximum operating pressure at the pump

bar

6.0

Weight

kg

2.4

REMKO PUMP GROUPS HGM / HGU

10