2.7

Delivery heights and electrical power

2

1

Fig. 7: Delivery heights and electrical power of the Wilo Stratos Para 25 / 1-7 T1pump

1: External operating mode via analogue-in 0-10V

2: External operating mode via pump shaft model (PSM)

3

Unit description

These pump groups HGM / HGU enable circulation

of the heat conducting medium via the inlet. The

pump group HGM regulates the temperature of the

heat conducting medium via a motorised mixing

valve. This pump group with controllable tempera-

ture is therefore ideal for operating normal heating

systems with temperature regulation. Temperature

regulation of the Inlet takes place depending on

the inlet and return temperatures of probes S12

and S11.

The pump groups comprise the following: Pump,

ball valve for inlet and return flow, thermometer for

inlet and return flow, check valve against the

heating cycle and thermal insulation.

The pump group HGM also has an integrated

mixing valve

The pump group with the heating cycle mixing

valve consists of the components displayed in

Fig. 8:

n

Front part of the insulation (1)

n

Rear part of the insulation (2)

n

Insulation of the pump (3)

n

Unit inlet (4) equipped with secondary circuit

ball valve, a motorised mixing valve and a ther-

mometer

n

Unit return flow (5) equipped with secondary

circuit ball valve with an integrated check valve

and a thermometer

2

1

4

3

5

Fig. 8: Unit components

The two insulation half-shells (1, 2) serve as heat

insulation for the pump group and therefore enable

energy to be saved. The pump insulation was

developed to guarantee heat insulation and to pre-

vent the electric motor from overheating. The

check valve that is integrated into the body of the

return flow's ball valve prevents incorrect circula-

tion when the pump is switched off.

REMKO PUMP GROUPS HGM / HGU

12