5

Troubleshooting

Fault

description

Cause

Remedy

Pump does

not run when

power supply

is switched

on

Electrical fuse

defective, pump

has no power

Check the fuses, eliminate the power interruption.

Pump makes

noises

Cavitation

caused by insuffi-

cient inlet pres-

sure

Increase the system pressure within the permissible area, check the

delivery height setting and set a lower height if necessary

Power

supply

undervoltage

Power supply

overloaded

The motor is switched off in the case of overvoltage or undervoltage. It

starts again automatically as soon as the voltage is again in the per-

mitted area. SSM relay is active. Off: 165 V AC / On: 195 V AC

Power

supply over-

voltage

Faulty feed from

the energy

supply company

Faulty feed from the energy supply company. The motor is switched off

in the case of overvoltage or undervoltage. It starts again automatically

as soon as the voltage is again in the permitted area. SSM relay is

active. Off: 265 V AC / On: 245 V AC

Motor

jammed

e.g. due to

deposits

If the motor jams, a maximum of 5 restarts at 30 second intervals take

place. If the motor remains jammed, it is switched off permanently. It can

only be switched back on again by switching off the power for more than

30 seconds and then switching it on again. The unjamming programme

runs during each start process. The SSM relay is active as long as the

internal error counter is not ZERO.

Motor over-

load

Deposits in the

pump

If the power consumption of the motor exceeds the limit for more than 60

seconds, the "Overload" error is reported. The motor is stopped and

started again after a 30 second pause. If no overloading occurs within

the next 2 minutes, the internal error counter is reset. Otherwise, the

motor is switched off permanently after 5 unsuccessful restarts. This can

only be reset by switching the power off for more than 30 seconds. The

SSM relay is active as long as the internal error counter is not ZERO

Short circuit/

earth

leakage

Motor defective

The motor is switched off after a short circuit. It is switched on again

after 30 seconds. The motor is switched off permanently after 5 short cir-

cuits. This can only be reset by switching the power off for more than 30

seconds. The SSM relay is active as long as the internal error counter is

not ZERO

Contact error The module is

not connected

correctly. Con-

nection between

motor and

module inter-

rupted

If the contact between the motor and the module fails, the motor is

switched off. A restart occurs after 30 seconds. After the motor has been

switched off for the fifth time, it is switched off permanently. This can

only be reset by switching the power off for more than 30 seconds. The

SSM relay is active as long as the internal error counter is not ZERO.

Running

empty

Air in the pump

The motor is switched off after a defined period of time when running

under dry running conditions. It starts again after a delay of 30 seconds.

If no dry run occurs within the next 2 minutes, the internal error counter

is reset. Otherwise, the motor is switched off permanently after 5 unsuc-

cessful restarts. This can only be reset by switching the power off for

more than 30 seconds. The SSM relay is active as long as the internal

error counter is not ZERO.