Technical data – REMKO ML 260 User Manual
Page 12

12
ML 260
ML 350
ML 520
ML 680
Nominal cooling capacity*
kW
2.59
3.50
5.27
6.80
Energy efficiency class cooling
C
C
D
D
Energy efficiency ratio
EER
2.82 2.82 2.61 2.61
Operational area (
size of room
), approx.
m³
80
110
160
230
Refrigerant R
407C
Injection pipe connection
Inches
(mm)
1/4 (6.35)
3/8 (9.52)
Suction pipe connection
Inches
(mm)
3/8 (9.52)
1/2 (12.7)
5/8 (16.0)
Refrigerant pipe, length max.
m
10
15
Refrigerant pipe, height max.
5
8
Refrigerant, base quantity
g
680
1050
1700
1730
Refrigerant, additional amount > 5 m
g/m
15
20
30
35
Power supply
V/Ph/Hz
230 / 1~ / 50
Nominal power consumption cooling *
kW
0.92
1.24
2.02
2.61
Nominal current consumption cooling* A
4.35
5.55
10.58
13.45
Respective indoor unit
ML 260-IT
ML 350-IT
ML 520-IT
ML 680-IT
Operating range
°C
+16 to +32
Circulating air volume per speed
m³/h 270/320/400
330/410/500
500/610/750
600/730/900
Protection type
IP
X0
Sound pressure level per speed **
dB(A)
33 / 36 / 41
35 / 38 / 42
36 / 40 / 44
38 / 41 / 46
Dimensions
height
mm
268
286
326
width mm
788
886 1096
depth mm
180
180 215
Weight kg
8
9
15
15
Respective outdoor unit
ML 260-AT
ML 350-AT
ML 520-AT
ML 680-AT
Operating range
°C
+21 to +45 (with optional winter regulation -10 to +45)
Circulating air volume, max.
m³/h
1620
1740
2520
3600
Protection type
IP
X4
Sound pressure level, max. **
dB(A)
50
51
54
58
Dimensions
height
mm
543
548
605
730
width mm
645
700
805
860
depth mm
265
275
305
325
Weight kg
29
35
53
76
Serial number
700....
701....
702....
703....
Ref. number
1618260
1618350
1618520
1618680
Power consumption in 500 hours
kWh
460
620
1010
1305
Technical Data
*
Room temperature DB 27°C, WB 19°C; outside temperature DB 35°C, WB 24°C
** Distance
1m