Technical data

Series

WLT 25

WLT 27

WLT 45

WLT 55

WLT 75

WLT 85

Operating mode

Chilled water wall unit for 2-pipe system

Nominal cooling capacity

1)

kW

2.04

2.73

4.38

5.81

7.05

8.55

Nominal heating capacity

2)

kW

4.07

5.38

8.61

11.95

13.92

17.13

Operating range (room volume), approx.

60

90

140

190

230

280

Setting range, room temperature

°C

+16 to +30

Operating range - indoor unit

°C

+16 to +35

Air flow rate per speed setting

m³/h 295/330/360 320/365/415 605/680/735 705/795/865 880/1100/1270 1090/1220/1400

Sound pressure level

3)

dB (A)

26/30/33

28/31/36

33/36/38

35/37/40

38/40/42

39/42/43

Power supply

V/Hz

230/1~/50

Protection class

IP

X0

Electr. nominal power consumption

1)

kW

0.03

0.03

0.06

0.06

0.08

0.09

Electr. nominal current consumption

1)

A

0.12

0.14

0.24

0.27

0.32

0.41

Operating medium

Water; max 35 % ethylene-glycol, max. propylene-glycol max. 35 %

Operating limits, medium - cooling

°C

+4 to +18

Operating limits, medium - heating

°C

+35 to +70

Max. operating pressure, medium

kPa

600

Minimum supply temperature, heating

°C

+40

Nominal flow rate, medium - cooling

1)

m³/h

0.35

0.46

0.80

1.00

1.22

1.49

Nominal flow rate, medium - heating

2)

m³/h

0.35

0.46

0.80

1.00

1.22

1.49

Rated pressure drop, internal

1)

kPa

9.5

20.5

21.0

22.5

21.7

33.5

Rated pressure drop, internal

2)

kPa

7.0

18.5

19.0

21.0

17.8

27.1

Medium connection, inlet

mm

12

15

18

Medium connection, outlet

mm

12

15

18

Medium content

l

0.81

0.96

1.07

1.96

2.41

2.93

Condensate drainage connection

mm

16.5

24.0

Dimensions - height

mm

298

305

360

360

365

365

width

mm

880

990

1172

1172

1450

1450

depth

mm

180

180

206

206

215

215

Weight

kg

8.6

10.4

16.0

17.6

24.1

25.1

Operating weight, approx.

kg

9.4

11.4

17.0

19.6

26.5

28.0

Serial number

467...

468...

469...

470...

472...

473...

EDP no.

1611725

1611727

1611745

1611755

1611775

1611785

1) Air inlet temperature TK 27 °C / FK 19 °C, medium inlet 12 °C, medium outlet 7 °C, 0 % glycol concentration, max. air flow rate
2) Air inlet temperature TK 20 °C, medium inlet 70 °C, medium outlet 60 °C, 0% glycol concentration, max. air flow rate
3) Distance 1m free field conditions

REMKO WLT