The control is implemented

through the 3-way valve assembly.

It comprises the electrically

actuated valve head and the valve

body. If the head is electrically

activated, it actuates the body,

which routes the medium into

the register. If the temperature is

reached then the head is switched

off and the medium is fed through

the bypass past the register.

The bypass serves to ensure

the minimum medium flow rate

for the chiller.

The time between being fully

open and fully closed can be

approx. three minutes.

NOTE

Valves for hydronic balancing

The calculated individual pressure

losses in the pipeline network

layout for each individual unit

are adjusted to the entire system

with pipe leg regulating valves to

be provided on-site. The nominal

flow rates for the medium adjust

to the necessary values as a

consequence of the pressure loss.

Anti-freeze protection

(accessories)

A water glycol mix is generally

used as medium for a cold water

system. Depending on the use to

which the glycol type and quantity

is put, the viscosity changes,

the loss in pressure increases and

the unit's cooling or heating

capacity reduces.

All system components must

be approved for use with glycol.

Diaphragm expansion vessel (MAG)

To avoid pressure fluctuations

during standstill because of

temperature changes, diaphragm

expansion vessels filled with

nitrogen (moisture neutral) must

be integrated in the system.

No moisture can condense in

the nitrogen filler.

NOTE

Safety valve

Safety valves limit excess operating

pressure due to excess warming

or overfilling of the operating

medium. The valve outlet requires

unobstructed draining into a drain

line. Applicable local disposal

ordinances must be observed if

glycol is used.

Automatic bleed valves

The unit has one or two manual

bleed valves on the collector pipe

of the register. The unit can be

bled separately after the system

has been filled. Automatic bleed

valves must also be installed

at the next highest point in

the collective lines.

During use and

disposal the product and safety

data sheets of the glycol type

which is used must be ob-

served.

CAUTION

Glycol tolerant air vent valves

are necessary when using

media that contain glycol.

CAUTION

Manual bleeding

Manual bleeding valve

Valve head

Valve body

Outlet Inlet

Condensate drainage connection

If the temperature falls below
the dew point, condensation will
form on the cooling fins during
cooling mode.

Below the register is a collection
tray, which must be connected
to a drain.

The condensate drainage line
provided by the customer is to
be installed with a minimum
incline of 2 %. (Fig. 6).
If necessary, fit vapour diffusion
tight insulation.

Route the condensate drainage
line of the unit freely into
the drain line. If the condensate
runs directly into a sewer
pipe, fit a trap to prevent any
unpleasant odours.

When operating the unit at
outside temperatures below
0 °C, ensure the condensate
line is laid to protect it against
frost. If necessary, install a pipe
heater.

Following installation, check
that the condensate run off is
unobstructed and ensure that
the line is durably leak tight.

6

Incline of the condensate line

2 % incline

The condensate hose is designed
to be connected on the left-hand side
(as viewed from the front).

17