Function test of heating operating
mode
1. Switch the power supply on.
2. Open all shut-off valves.
3. Switch on the heating system
and the corresponding
circulation pump. The outlet
temperature must lie between
+35 and +70 °C.
4. Use the remote control to
switch on the unit and select
the heating mode, maximum
fan speed and highest target
temperature.
5. Measure and record all
the required values in the
commissioning report and
check the safety functions.
6. Check the indoor unit control
system using the functions
described in the chapter
"Operation". Timer,
temperature setting, fan
speeds.
Final tasks
■
Reassemble all disassembled
parts.
■
Familiarise the operator with
the system.