REMKO WLT 25 User Manual
Page 21
Cooling capacity
Medium inlet
Medium nominal
5 °C
7 °C
9 °C
11 °C
13 °C
Cooling capacity
Flow
volume
[m
3
/h]
Pressure
loss
[kPa]
Q
K
[kW]
Q
S
[kW]
Q
K
[kW]
Q
S
[kW]
Q
K
[kW]
Q
S
[kW]
Q
K
[kW]
Q
S
[kW]
Q
K
[kW]
Q
S
[kW]
WLT 25
0.35
9.5
2.35
1.97
2.04
1.62
1.77
1.41
1.49
1.24
1.17
1.02
WLT 27
0.46
20.5
3.20
2.59
2.73
2.15
2.29
1.83
1.77
1.48
1.46
1.17
WLT 45
0.80
21.0
4.99
4.22
4.38
3.56
3.71
2.95
3.24
2.39
2.72
1.98
WLT 55
1.00
22.5
6.42
4.93
5.81
4.54
5.17
4.19
4.37
3.74
3.65
3.18
WLT 75
1.22
21.7
8.08
5.51
7.05
5.09
6.37
4.64
5.88
4.13
5.20
3.73
WLT 85
1.49
33.5
9.40
6.13
8.55
5.61
7.58
5.13
6.67
4.69
5.14
4.19
Air inlet temperature TK 27 °C / FK 19 °C, 0 % Glycol concentration, max. air flow
Q
K
= Cooling capacity, total
Q
S
= Cooling capacity, sensible
Heating capacity
Medium inlet
nominal medium
40 °C
45 °C
50 °C
55 °C
60 °C
65 °C
70 °C
Heating capacity
Flow
rate
[m
3
/h]
Pressure
drop
[kPa]
Q
H
[kW]
Q
H
[kW]
Q
H
[kW]
Q
H
[kW]
Q
H
[kW]
Q
H
[kW]
Q
H
[kW]
WLT 25
0.35
7.0
1.59
2.28
2.60
2.95
3.33
3.67
4.07
WLT 27
0.46
18.5
2.18
2.64
3.26
3.71
4.23
4.80
5.38
WLT 45
0.80
19.0
3.54
4.35
5.17
5.98
6.86
7.72
8.61
WLT 55
1.00
21.0
4.71
5.94
7.20
8.39
9.58
10.74
11.95
WLT 75
1.22
17.8
6.17
7.36
8.75
9.99
11.40
12.58
13.92
WLT 85
1.49
27.1
7.64
9.11
10.78
12.29
14.05
15.53
17.13
Air inlet temperature TK 20 °C, 0 % Glycol concentration, max. air flow
Q
H
= Heating capacity, total
21