Appendix g - vcm lon parameters, Pt-link ii interface, Pt-link ii lon – Orion System PT-Link II LON User Manual
Page 55: Technical guide 55, Snvts for the vcm controller
PT-Link II Interface
PT-Link II LON
®
Technical Guide
55
Appendix G - VCM LON Parameters
SNVTs for the VCM Controller
Binary Output SNVTs are SNVT_lev_disc
All other SNVTs are SNVT_count_inc_f
Parameter
Name
Object
Description
Limits
Supply
Air Sensor
Offset
SaTpOst
Analog
Input
If the Supply Air
Temperature
Sensor is reading
incorrectly, you can
use this option to
enter an offset
temperature to
adjust the Sensor’s
Temperature.
-100
100
Unoccupied
Cooling
Offset
UnClOst
Analog
Input
During the
Unoccupied Mode
of Operation, this
Setpoint spreads
the Occupied
Cooling Setpoint
out by a user
adjustable amount.
If you do not want
Cooling to operate
during the
Unoccupied Mode,
use the default
setting of 30°F for
these setpoints.
0
30
Unoccupied
Heating
Offset
UnHtOst
Analog
Input
During the
Unoccupied Mode
of Operation, this
Setpoint spreads
the Occupied
Heating Setpoint
out by a user
adjustable amount.
If you do not want
Heating to operate
during the
Unoccupied Mode,
use the default
setting of 30°F for
these setpoints.
0
30
Dewpoint
Setpoint
DptSt
Analog
Input
If the outdoor
dewpoint rises
above this setpoint,
the unit will
activate the
Dehumidifi cation
Demand.
35
80
SNVTs for the VCM Controller
Binary Output SNVTs are SNVT_lev_disc
All other SNVTs are SNVT_count_inc_f
Parameter
Name
Object
Description
Limits
Indoor
Humidity
Setpoint
InRhSt
Analog
Input
If the indoor
humidity rises
above this setpoint,
the unit will
activate the
Dehumidifi cation
Demand.
0
100
Warm Up
Setpoint
WmupSt
Analog
Input
In a VAV
application, upon
entering the
occupied mode, the
Warm-up Demand
will be activated
if the return air
temperature falls
one degree below
this setpoint.
50
90
Wet Bulb
Setpoint
WtblSt
Analog
Input
The economizer is
enabled if the out-
door temperature
or wetbulb falls
below this setpoint.
0
80
Bad Supply
Air Sensor
SaTpAlm
Binary
Output
Alarm that
indicates a failure
in the supply air
sensor.
CO
2
Sensor
Installed
CO2Cfg
Binary
Output
Status that
indicates the CO
2
function has been
confi gured.
Cooling
Demand
ClDmnd
Binary
Output
Status that
indicates a demand
for cooling.
Cooling
Enabled
ClEnbl
Binary
Output
Status that indicates
mechanical cooling
is enabled.
Economizer
Enabled
EcoEnbl
Binary
Output
Status that indicates
the economizer is
enabled.
Fan Start
Up Delay
FanDly
Binary
Output
Status that indicates
the fan is
commanded to run,
but it is in the start
up delay mode.
Fan
Proving
Alarm
PofAlm
Binary
Output
Alarm that
indicates a failure
in the fl ow of the
VFD blower.
Heating
Demand
HtDmnd
Binary
Output
Status that indicates
a demand for
heating.