PT-Link II Interface

3

PT-Link II LON

®

Technical Guide

The OE368-23-LON, PT-Link II LON, provides bi-directional communi-
cation between ONE* of the following types of Orion controllers—RNE,
VCB-X, VCM-X, SA, VCM, MUA II, or VAV/CAV:

RNE Controller (SS1045)

VCB-X Controller (SS1051)

VCM-X Controller (SS1026, SS1030, SS1032,
SS1033, SS1034, Y200920)

SA Controller (Y200921)

VCM Controller (SS1016, Y200409, Y200616, Y200822)

** MUA II Controller (Y200405); VAV/CAV Controller
(Y200301)

To determine what controller you have, you must look at the label located
on the controller EPROM. If the controller label does not match any of
the SS or Y numbers listed above, your controller will not work with
the PT-Link II LON

®

.

*NOTE: The PT-Link II LON device can be used to connect to only

one Orion controller. If more than one Orion controller
is present in a system, each one will require a PT-Link
II LON device for integration with a LON protocol net-
work.

**NOTE: Documentation is available for MUA II/VAV/CAV on

our Orion Controls website: www.orioncontrols.com

Data Sharing

The PT-Link II LON interface provides the following data sharing
capabilities:

Provides values from points on the Orion side of the

gateway to LON

®

devices as if the values were

originating from LON

®

objects.

Allows LON

®

devices to modify point values on the

Orion controller side of the PT-Link II LON

®

by using

standard

LON

®

write services.

Hardware Specifi cations

Table 1 contains the hardware specifi cations for the PT-Link II LON

®

interface.

Technical Data

LON® Loop

TP/FT-10 (78 Kps)

Controller Loop

RS-485, 9600 Baud Rate

Network Protocol

LONWorks®

Protocol
(WattMaster Loop)

HSI Open Protocol Token Passing

Power Input Voltage

24 VAC

Power Consumption

10 VA Maximum

Operating Temp

-30°F to 150°F

Operating Humidity

90% RH Non-Condensing

Weight

4.7 oz.

Table 1: PT-Link II LON

®

Interface Technical Data

System Requirements

The

PT-Link II LON

®

interface is packaged and assembled

as surface mount. Surface mount components are included

for your convenience.

Computer running Microsoft Windows

TM

operating

system.

Ethernet Crossover Cable (supplied).

PT-Link LON & RUINET software—included on

CD-ROM and also downloadable from www.orioncontrols.

com

General Information

Revised 10/11/12