Appendix c - vcb-x lon parameters, Pt-link ii lon, Technical guide – Orion System PT-Link II LON User Manual
Page 34: Pt-link ii interface 34

PT-Link II LON
®
Technical Guide
PT-Link II Interface
34
Appendix C - VCB-X LON Parameters
SNVTs for the VCB-X Controller
Binary Output SNVTs are SNVT_lev_disc
all other SNVTs are SNVT_count_inc_f
Parameter
Name
Object
Description
Limits
Outdoor
Wetbulb
OaWtbl
Analog
Output
Current cal-
culated value
of the outdoor
wetbulb
temperature.
Preheat
Relay
Setpoint
PreHtAmb
Analog
Input
If the Supply
Fan is ener-
gized this is the
temperature
at which the
Preheat Relay
will activate.
Operates only
in the Occupied
Mode.
-30
70
Proof of Flow
Alarm
PofAlm
Binary
Output
Indicates no
Proof of Water
Flow.
Reheat
Enabled
RehtEnbl
Binary
Output
Modulating
Hotgas Reheat
Enabled.
Reheat Valve
Position
RtVlvPos
Analog
Output
Current
position of
MHGRV
modulating
hot gas reheat
valve.
Missing
Reheat
Module
MisMH-
GRV
Binary
Output
Indicates that
the MHGRV
Module is not
communicating
with the VCB-
X Controller.
Return Air
CFM
RaCFM
Analog
Output
Current Return
Airfl ow
Measurement.
Missing
Return Air
CFM Sensor
RaCfmSr
Binary
Output
Indicates
that the Return
Air CFM
Sensor is not
detected.
Return Air
Damper
Position
RaDmp
Analog
Output
Current Return
Air Damper
position.
Return Air
Humidity
RaRH
Analog
Output
Current value
of the Return
Air Humidity
Sensor.
Return Air
Temperature
RaTp
Analog
Output
Current value
of the return
temperature
sensor.
SNVTs for the VCB-X Controller
Binary Output SNVTs are SNVT_lev_disc
all other SNVTs are SNVT_count_inc_f
Parameter
Name
Object
Description
Limits
Return Air
Temperature
Sensor Offset
RaTpOst
Analog
Input
If the Return
Temperature
Sensor is
reading
incorrectly, use
this to enter an
offset to adjust
the Sensor’s
Temperature.
-100
100
Bad Return
Air Sensor
RaTpAlm
Binary
Output
Indicates a
failure of the
Return Air
Sensor.
Return Bypass
Damper
Position
RetBydmp
Analog
Output
Current Return
Bypass Damper
position.
Schedule
Force
SchdFrc
Analog
Input
0 = Auto (uses
controller’s
schedule)
1 = Forced
Occupied
2 = Forced
Unoccupied
0
2
Current Slide
Adjust Offset
SldAdOfs
Analog
Output
Current Slide
Adjust Offset
value.
Smoke Alarm
/ Emergency
Shutdown
SmokeAlm
Binary
Output
Indicates the
Smoke sen-
sor has been
activated. This
will shut down
the unit.
Space
Temperature
SpcTp
Analog
Output
Current value
of the space
temperature
sensor.
Space
Temperature
Offset
SpcTpOst
Analog
Input
If the Space
Temperature
Sensor is
reading
incorrectly, use
this option to
enter an offset
to adjust the
Sensor’s
Temperature.
-100
100
Space
Temperature
Sensor
Lost
SpcTpAlm
Binary
Output
Indicates
a failure of the
Space Tempera-
ture Sensor.
Static
Pressure
StaticPr
Analog
Output
Current Static
Pressure.
Static
Pressure
Setpoint
StatPrSt
Analog
Input
Current Static
Pressure
Setpoint.
.10
3.0
Revised 7/7/14