Appendix e - vcm-x lon parameters, Pt-link ii lon, Technical guide – Orion System PT-Link II LON User Manual
Page 48: Pt-link ii interface 48, Vcm-x pt-link ii lon, Property identifi er

PT-Link II LON
®
Technical Guide
PT-Link II Interface
48
VcmxExternal Relays2-4Bits::= BIT STRING {
ExpansionBoard3Relay1
(0),
ExpansionBoard3Relay2
(1),
ExpansionBoard3Relay3
(2),
ExpansionBoard3Relay4
(3),
ExpansionBoard4Relay1 (4),
ExpansionBoard4Relay2
(5),
ExpansionBoard4Relay3
(6),
ExpansionBoard4Relay4
(7)
}
VcmxAlarmStatusBits ::= BIT STRING {
Alarm
Group1
(0),
Alarm
Group2
(1),
Alarm
Group3
(2),
Alarm
Group4
(3),
Alarm
Group5
(4)
}
VcmxAlarmGroup1Bits ::= BIT STRING {
SupplyTempSensorFailure
(0),
LostOutdoorTempSensorSignal
(1),
LostSpaceTempSensorSignal
(2),
ModuleAlarm
(3),
DemandVentilationAlarm (4),
OutdoorCFMSensorFailure
(5),
ReturnTempSensorFailure
(6)
}
VcmxAlarmGroup2Bits ::= BIT STRING {
MechanicalCoolingAlarm
(0),
MechanicalHeatingAlarm
(1),
FanProvingAlarm
(2),
DirtyFilterDetected
(3),
SmokeDetected (4)
}
VcmxAlarmGroup3Bits ::= BIT STRING {
LowSupplyAirTempAlarm
(0),
HighSupplyAirTempAlarm
(1),
LowControlTempAlarm
(2),
HighControlTempAlarm
(3)
}
VcmxAlarmGroup5Bits ::= BIT STRING {
AirTempSensorFailure
(0),
NoEconWhenItShould
(1),
EconWhenItShouldNot
(2),
DamperFailure
(3),
ExcessOutdoorAir
(4)
}
Appendix E - VCM-X LON Parameters
VCM-X PT-Link II LON
®
Property Identifi er:
The PT-Link II LON
®
Link amends the following property identity to
the LON
®
property identifi er.
LONPropertyIdentifi er :
WattLONScheduleForce ::= ENUMERATED {
NormalOperation
(0),
ForceOccupied
(1),
ForceUnoccupied
(2)
}
VcmxUnitMode ::= ENUMERATED {
Unoccupied
(0),
RemoteContactOccupied (1),
NormalScheduleOccupied
(2),
PushButtonOrZoneOverride
(3),
HolidayModeActive
(4),
UnoccupiedZoneDemand
(5),
RemoteScheduleOverride (6),
CurrentOutputForceMode
(7),
SATHighOrLowCutOff
(8),
CO2OverrideInProgress
(9),
PurgeModeActive
(10)
}
VcmxControlStatusBits ::= ENUMERATED {
Off
(0),
Vent
(1),
Cool
(2),
Heat
(3),
Dehum
(4),
Dehum
Cool
(5),
Dehum
Heat
(6),
Warm
Up
Mode
(7)
}
VcmxOnBoardRelaysBits ::= BIT STRING {
OnBoardRelay1
(0),
OnBoardRelay2
(1),
OnBoardRelay3
(2),
OnBoardRelay4
(3),
OnBoardRelay5
(4)
}
VcmxExternal Relays1-2Bits::= BIT STRING {
ExpansionBoard1Relay1
(0),
ExpansionBoard1Relay2
(1),
ExpansionBoard1Relay3
(2),
ExpansionBoard1Relay4
(3),
ExpansionBoard2Relay1
(4),
ExpansionBoard2Relay2
(5),
ExpansionBoard2Relay3
(6),
ExpansionBoard2Relay4
(7)
}
Revised 7/10/14