Changing the confi g.csv file – Orion System PT-Link II LON User Manual
Page 11
PT-Link II Interface
PT-Link II LON
®
Technical Guide
11
12.) At the next screen, (Figure 15), type
again.
Figure 15: Download new Confi g.csv fi le
NOTE: The utility will indicate when downloading is
complete. DO NOT reset the PT-Link II until this mes-
sage is displayed, as this will corrupt the PT-Link II .
NOTE: The Remote Filename option must always be named
“confi g.csv” for confi gurations; otherwise, it will be
ignored by the PT-Link II .
13.) Once the download is complete, restart the PT-Link II by
cycling power or press
to get back to the RUINET Main Menu
and then type
option to save the new confi guration fi le and restart
RUINET. It is possible to do multiple downloads to the PT-Link II
before resetting it. There will be a start-up period where you will be
unable to connect to the PT Link.
14.) From the RUINET Main Menu, type
for the Data Array
Overview. The Data Array Overview Screen will display (Figure 16).
Changing the Confi g.csv File
Figure 16: Data Array Overview Screen
15.) This screen (Figure 16) will verify communication to the HVAC
units. Lines 1 & 2 should always be present. After a start-up period
of approximately 4 minutes, you will see 2 additional lines as shown.
This screen represents the PT Link communicating with 1 HVAC unit.
16.) Once these steps have been completed and you have verifi ed
that the reconfi gured PT Link has established communication to the
HVAC unit, it can now be added to the BAS network.