Appendix g - vcm lon parameters, Pt-link ii interface, Pt-link ii lon – Orion System PT-Link II LON User Manual
Page 53: Technical guide 53, Snvts for the vcm controller
PT-Link II Interface
PT-Link II LON
®
Technical Guide
53
Appendix G - VCM LON Parameters
SNVTs for the VCM Controller
Binary Output SNVTs are SNVT_lev_disc
All other SNVTs are SNVT_count_inc_f
Parameter
Name
Object
Description
Limits
Application
Software
Version
AppVer
Analog
Output
Current version of the
software in the unit.
Alarm
Status
AlrmSts
Analog
Output
See
page
58.
Unit Mode
UnitMode
Analog
Output
See
page
58.
Control
Status
CtrlSts
Analog
Output
Current operational
status.
Control
Temperature
CtrlTp
Analog
Output
Current value of the con-
trol temperature sensor.
Occupied/
Mode
Enable
Cooling
Setpoint
Mirror
ClSt
Analog
Output
Occupied/ Mode
Enable Cooling Setpoint
Mirror.
Duct Static
Pressure
DuctPr
Analog
Output
Current value of the duct
static pressure sensor.
Economizer
Position
EcoPos
Analog
Output
Current position of the
economizer damper.
External
Relays 1-2
ExRlys12
Analog
Output
See
page
58.
External
Relays 3-4
ExRlys34
Analog
Output
See
page
58.
Indoor
Humidity
InRh
Analog
Output
Current value of the
indoor humidity sensor.
Occupied/
Mode
Enable
Heating
Setpoint
Mirror
HtSt
Analog
Output
Occupied/ Mode
Enable Heating Setpoint
Mirror.
On Board
Relay
OnRlys
Analog
Output
See
page
58.
Outdoor Air
Humidity
OaRh
Analog
Output
Current value of the out-
door humidity sensor.
Outdoor Air
Temperature
OaTp
Analog
Output
Current value of the out-
door temperature sensor.
Outdoor Air
Wetbulb
OaWtbl
Analog
Output
Current calculated value
of the outdoor wetbulb
temperature.
Relief
Pressure
RfPr
Analog
Output
Current value of the
building pressure sensor.
Return Air
CO
2
Level
CO2Level
Analog
Output
Current value of the CO
2
sensor.
Return Air
Temperature
RaTp
Analog
Output
Current value of the re-
turn temperature sensor.
SNVTs for the VCM Controller
Binary Output SNVTs are SNVT_lev_disc
All other SNVTs are SNVT_count_inc_f
Parameter
Name
Object
Description
Limits
Space
Temperature
SpcTp
Analog
Output
Current value of
the space tempera-
ture sensor.
Supply Air
Temperature
SaTp
Analog
Output
Current value of
the supply air
temperature sensor.
Temperature
Demand
TpDmnd
Analog
Output
Based on the com-
parison between
the current Control
Temperature and
the Heating or
Cooling Setpoint
Temperatures.
Does not work for
supply air control.
VFD
Blower Fan
VfdBwPos
Analog
Output
Current position
of the VFD blower
fan signal.
VFD Relief
Fan
VfdExPos
Analog
Output
Current position of
the VFD relief
fan signal.
Modulating
Gas Valve
Position
MdHt2Pos
Analog
Output
Current position
of MODGAS II
modulating gas
valve control.
Reheat
Value
Position
Rt2Pos
Analog
Output
Current position of
MHGRV
modulating hot
gas reheat valve
control.
Alarm
Group 1
AlrmGrp1
Analog
Output
See
page
58.
Alarm
Group 2
AlrmGrp2
Analog
Output
See
page
58.
Alarm
Group 3
AlrmGrp3
Analog
Output
See
page
58.
Dewpoint
Setpoint
Mirror
DptStM
Analog
Output
Mirror of the DPtSt
“read only.”
Indoor RH
Setpoint
Mirror
InRhStM
Analog
Output
Mirror of the
InRhSt “read only.”
Modulating
Cool
Position
MdClPos
Analog
Output
Current position of
the modulating
cooling signal
(Chilled water or
digital compressor).
Modulating
Heat
Position
MdHtPos
Analog
Output
Current position of
the modulating
heating signal
(hot water or SCR
heat).
Bypass
Damper
Position
ByPasDmp
Analog
Output
Current position of
the bypass damper
signal.