Appendix C - VCB-X LON Parameters

SNVTs for the VCB-X Controller

Binary Output SNVTs are SNVT_lev_disc

all other SNVTs are SNVT_count_inc_f

Parameter

Name

Object

Description

Limits

Modulating

Heating

Position

MdHtPos

Analog

Output

Current

position of the

modulating

heating signal

(hot water or

SCR heat).

Missing

MODGAS

Module

MisMDGAS

Binary

Output

Alarm that

indicates that

the MODGAS

module is not

communicating

with the VCB-

X Controller.

Morning

Warm-Up

Return Air

Target

Setpoint

WmupTg

Analog

Input

If confi gured,

upon entering

the

occupied mode,

the Warm-up

Demand will be

activated if the

return air tem-

perature is one

degree below

this setpoint.

50

90

Occupied

Cooling

Setpoint

OcpClSt

Analog

Input

If the control

temperature

rises one degree

above this

setpoint, the

control will ac-

tivate the cool-

ing demand. If

the control

temperature is

the Supply Air

Sensor, then the
cooling demand

is always

active.

1

110

Occupied

Heating

Setpoint

OcpHtSt

Analog

Input

If the control

temperature

drops one

degree below

this setpoint,

the control

will activate

the heating

demand. If the

control

temperature

is the Supply

Air Sensor, then

there is no

heating

demand.

1

110

SNVTs for the VCB-X Controller

Binary Output SNVTs are SNVT_lev_disc

all other SNVTs are SNVT_count_inc_f

Parameter

Name

Object

Description

Limits

Hood On

Outdoor

Air Cooling

Setpoint

OaClSt

Analog

Input

This is the

Cooling Mode

Enable

Setpoint used

only in Hood

On Mode.

1

110

Hood On

Outdoor

Air Heating

Setpoint

OaHtSt

Analog

Input

This is the

Heating Mode

Enable

Setpoint used

only in Hood

On Mode.

1

110

Outdoor Air

CFM

OaCFM

Analog

Output

Current

Outdoor

Airfl ow

Measurement

Minimum

Desired

Outdoor Air

CFM

OACfmMin

Analog

Input

Minimum

Outdoor Air-

fl ow

CFM Setpoint

.10K

200K

Missing Out-

door Air CFM

Sensor

OaCfmAlm

Binary
Output

Indicates

Outdoor Air

CFM Sensor is

not detected.

Outdoor

Humidity

OaRh

Analog

Output

Current value

of the Outdoor

Humidity

Sensor.

Outdoor Air

Dewpoint

OaDewPt

Analog

Output

Current calcu-

lated Outdoor

Air Dewpoint.

Outdoor Air

Temperature

OaTp

Analog

Output

Current value

of the

outdoor

temperature

sensor.

Outdoor Air

Temperature

Offset

OaTpOst

Analog

Input

If the Outdoor

Temperature

Sensor is read-

ing

incorrectly, use

this to enter an
offset to adjust

the Sensor’s

Temperature.

-100

100

Minimum

Outside Air

CFM Dead-

band

OacfmDb

Analog

Input

The Deadband

is used both

above and

below the

Outdoor Air

CFM setpoint

to help prevent

hunting.

10

1000

Outdoor Air

Temperature

Sensor Lost

OaTpAlm

Binary
Output

Indicates a

failure of the

Outdoor Air

Temperature

Sensor.