Online power, Appendix a - specifications – OnLine Power Phase Stabilizer User Manual
Page 80
OnLine Power
6002-032 REV H
A-1
APPENDIX A - SPECIFICATIONS
TABLE A-1
SPECIFICATIONS
POWER-REG AND ULTRA-REG
NOMINAL INPUT VOLTAGE
208 VAC
480 VAC
INPUT VOLTAGE RANGE
154 - 229
355 - 528
MAXIMUM INPUT VOLTAGE
229 528
NOMINAL RATED CURRENT (A)
See Table 2-1
FREQUENCY (Hz)
60
OUTPUT VOLTAGE REGULATION
± 3% Typical, ± 4% Maximum
LINE-TO-LINE VARIATION
LESS THAN 2%
RESPONSE TIME
1 Cycle Typical
FILTERS:
INPUT
OUTPUT
YES
Optional
COOLING REQUIREMENT (BTU/hr)
See Table 2-1
WEIGHT lbs (kg) (estimated)
See Table 2-1
OUTPUT VOLTAGE
208Y120 VAC or 480Y277 VAC
CAPACITY (KVA)
15, 30, 50, 75, 100, 125, 150,
175, 200, 225, 250, 300, 400 kVA
NUMBER OF PHASES
3
SURGE RATING
200% of Full Load for 10 Seconds
1000% of Full Load for 1 Cycle
HARMONICS ADDED
1% Maximum
POWER FACTOR
Greater Than 96%
AMBIENT TEMPERATURE °F (°C)
80 (26.7)
SIZE H X W X D in. (cm)
See Table 2-1