On-line power – OnLine Power Phase Stabilizer User Manual
Page 22
On-Line Power
6002-032 REV H
1-13
1-4-5 Input
Filter
The Input filter is installed on the primary side of the transformer. The input filter consists of a resistor/capacitor
network which acts as a large snubber circuit to eliminate high frequency impulses from entering the power
system. See Illustration 1-9.
H1
H2
H3
(L1)
(L2)
(L3)
R3
R2
R1
R6
R5
R4
C1
C2
C3
INPUT FILTER WIRING
ILLUSTRATION 1-9
1-4-6 Output
Filter
The Output filter is installed on the transformer secondary. It consists of a capacitor network which prevents
noise from being fed back to the unit from noise generating loads. See Illustration 1-10. Output filters are
standard on the Phase Stabilizer and optional on other models.
X0
X3
X2
X1
C6
C5
C4
OUTPUT FILTER WIRING
ILLUSTRATION 1-10