2-2 FLOOR

LOADING

Sizes and weights of units are listed in the following tables. Provide a floor with strength sufficient for loads
specified.

TABLE 2-5

POWER-REG AND ULTRA-REG FLOOR LOADING

kVA SIZE

INPUT

VOLTAGE

FLOOR LOADING

lbs/sq ft (kg/sq m)

kVA SIZE

INPUT

VOLTAGE

FLOOR LOADING

lbs/sq ft (kg/sq m)

15

208

128 (628)

150

208

129 (489

480

480

161

(788)

30

208 160

(788)

175

208 152

(563)

480

480

126

(464)

50

208 146

(710)

200

208 179

(662)

480

480

134

(497)

75

208 176

(862)

225

208 202

(746)

480

480

143

(530)

100 208

108

(414) 250 208

220

(811)

480

208 (1013)

480

161 (597)

125 208

121

(464) 300 208

260

(960)

480 148

(723)

480 175

(646)

TABLE 2-6

CONSTANT POWER 18 FLOOR LOADING

kVA SIZE

INPUT

VOLTAGE

FLOOR LOADING

lbs/sq ft (kg/sq m)

15 208

106

(520)

480

30 208

117

(571)

480

50 208

184

(899)

480

75 208

215

(1049)

480

100 480

250

(1221)