2-2 FLOOR
LOADING
Sizes and weights of units are listed in the following tables. Provide a floor with strength sufficient for loads
specified.
TABLE 2-5
POWER-REG AND ULTRA-REG FLOOR LOADING
kVA SIZE
INPUT
VOLTAGE
FLOOR LOADING
lbs/sq ft (kg/sq m)
kVA SIZE
INPUT
VOLTAGE
FLOOR LOADING
lbs/sq ft (kg/sq m)
15
208
128 (628)
150
208
129 (489
480
480
161
(788)
30
208 160
(788)
175
208 152
(563)
480
480
126
(464)
50
208 146
(710)
200
208 179
(662)
480
480
134
(497)
75
208 176
(862)
225
208 202
(746)
480
480
143
(530)
100 208
108
(414) 250 208
220
(811)
480
208 (1013)
480
161 (597)
125 208
121
(464) 300 208
260
(960)
480 148
(723)
480 175
(646)
TABLE 2-6
CONSTANT POWER 18 FLOOR LOADING
kVA SIZE
INPUT
VOLTAGE
FLOOR LOADING
lbs/sq ft (kg/sq m)
15 208
106
(520)
480
30 208
117
(571)
480
50 208
184
(899)
480
75 208
215
(1049)
480
100 480
250
(1221)