On-line power – OnLine Power Phase Stabilizer User Manual
Page 31

On-Line Power
6002-032 REV H
2-3
TABLE 2-2
SINGLE PHASE POWER REG PLANNING SPECIFICATIONS
NOMINAL INPUT VOLTAGE
208
480
INPUT VOLTAGE RANGE
154 – 229
355 – 528
MAXIMUM INPUT VOLTAGE
229
528
FREQUENCY (Hz)
60
AMBIENT TEMPERATURE °F (°C)
80 (26.7)
kVA SIZE
INPUT
VOLTAGE
NOMINAL RATED
CURRENT
COOLING
BTU/hr
WEIGHT lbs (kg)
SIZE H x W x D in. (cm)
WITHOUT PACKAGING
10
208
42
1364
350 (159)
32 X 26.5 X 17
(81 X 67 X 43)
480 18
20 208
42
2729 400
(181)
480 18
30 208
83
4080 500
(227)
480 36
50
208
139
6800
700 (318)
40.5 X 31.5 X 22
(103 X 80 X 56)
480 60
75 480
90
10200 850
(386)
100 480
120
13600 1000
(454)
TABLE 2-3
CONSTANT POWER 18 SITE PLANNING SPECIFICATIONS
NOMINAL INPUT VOLTAGE
208
480
INPUT VOLTAGE RANGE
154 – 229
355 – 528
MAXIMUM INPUT VOLTAGE
229
528
FREQUENCY (Hz)
60
AMBIENT TEMPERATURE °F (°C)
80 (26.7)
kVA SIZE
INPUT
VOLTAGE
NOMINAL RATED
CURRENT
COOLING
BTU/hr
WEIGHT lbs (kg)
SIZE H x W x D in. (cm)
WITHOUT PACKAGING
15
208
42
2040
520 (236)
42 X 32 X 22
(107 X 81 X 56)
480 18
30 208
83
4080 570
(259)
480 36
50 208
139
6800 900
(408)
480 60
75
208
208
10200
1050 (476)
42 X 32 X 27
(107 X 81 X 69)
480 90
100 480
120
13600 1220
(549)