On-line power – OnLine Power Phase Stabilizer User Manual
Page 34
On-Line Power
6002-032 REV H
2-6
TABLE 2-7
PHASE STABILIZER FLOOR LOADING
kVA SIZE
INPUT
VOLTAGE
FLOOR LOADING
lbs/sq ft (kg/sq m)
kVA SIZE
INPUT
VOLTAGE
FLOOR LOADING
lbs/sq ft (kg/sq m)
15
208
82 (399)
150
208
134 (513)
480
480
168
(822)
30
208 102
(500)
175
208 155
(597)
480
480
125
(480)
50
208 143
(701)
200
208 181
(696)
480
480
134
(513)
75
208 184
(899)
225
208 206
(778)
480
480
142
(546)
100 208
112
(431) 250 208
220
(845)
480 192
(934)
480 164
(629)
125 208
121
(464) 300 208
259
(994)
480 161
(788)
480 172
(662)
400
480
188
(724)
TABLE 2-8
SINGLE PHASE POWER REG FLOOR LOADING
kVA SIZE
INPUT VOLTAGE
FLOOR LOADING lbs/sq ft (kg/sq m)
10 208
97
(35.3)
480
20 208
111
(40.2)
480
30 208
139
(50.4)
480
50 208
194
(71)
480
75 480
236
(86)
100 480
278
(101)
2-3
CABLE ACCESS AND FLOOR LAYOUT
2-3-1 Cable
Access
Cable access to the Power-Reg, Ultra-Reg and Phase Stabilizer, sizes 100 to 400 kVA, is through a 4” diameter
hole in the right and left sides of the unit throught which the input and output cables can be passed. Cable
access to the Phaze Stabilizer, sizes 15 to 75 kVA, and the Constant Power 18 is through an opening in the left
and right side of the unit. See Illustrations 2-1 and 2-2.