Online power, Warning – OnLine Power Telecommunication User Manual
Page 53

OnLine Power
C-2
REV A
• Load Testing
• Load Testing shall only be performed as a bench test.
• While on open circuit, place 100 amp load across each battery for a period of 30 seconds.
• Measure and record end of discharge (E.O.D.) voltage at 30 seconds.
• Calculate average and compare results against value of 10.95 for Type PRC 12120X E.O.D.@ 30
Seconds and 100 amp load.
• If calculated average E.O.D. of group is observed as being normal, identify and replace individual
batteries with values that are 10% less than the group average.
• General Equipment Requirements.
• Digital voltmeter- 3 1/2 digit, minimum 0.25% accuracy.
• Load tester (100 amps) with digital voltage readout, minimum 0.25% accuracy.
• Thermometer-
thermocouple,
contact type, 1 0 C accuracy.
• Battery Date Coding.
• The manufacturer stamps the Negative terminal post of the battery, with the month and year date
code.
• Shelf life is based on normal storage temperature conditions, 66
o
F ~ 90
o
F, and requires recharging
every 6 months from the last full charge date.
WARNING!
BATTERY SHELF TIME, WHEN STORED UNDER TEMPERATURE
CONDITIONS OF 66
O
F ~ 90
O
F, IS FIVE ( 5 ) MONTHS MAXIMUM AFTER THE
SHIP DATE.
BATTERY MUST BE RECHARGED AFTER THIS DATE OTHERWISE THEY
WILL BE DAMAGED.
THE SHIP DATE IS PART OF THE SERIAL NUMBER,
EXAMPLE S/N 00 L7 02 00####
YEAR MONTH UNIT I.D. NUMBER