Online power – OnLine Power Telecommunication User Manual
Page 51

OnLine Power
B-6
REV A
B-7
INSTALLATION KIT (50FT) /60 HZ LIST 48 (Comcode 408479269, P/N 9100-1244)
The List 48 Installation Kit/60 Hz consists of conduits, fitting, and electrical power wires for connections to other
cabinets that are separated up to 50 ft. The List 48 is included as part of the List 1, 2, 3, 4, 5, 6, 7, 8, 17, 18, 19, 20,
21, 22, 23, and 24. The List 48 contains the following components:
List 48 Description
QTY
PART NO.
3/4” FLEXIBLE LIQUID TIGHT CONDUIT
125 FT
3/4” FLEXIBLE LIQUID TIGHT CONDUIT
100 FT
3/4” LIQUID TIGHT FLEXIBLE METAL CONDUIT SEAL RING
10
T&B 5263
3/4” LIQUID TIGHT FLEXIBLE METAL CONDUIT FITTINGS, STR
10
T&B 5333
AC POWER CABLES 12 AWG
200 FT
THHN-BLK-12-STR
AC POWER CABLES 12 AWG
200 FT
THHN-WHT-12-STR
AC POWER CABLES 12 AWG
200 FT
THHN-GRN-12-STR
6 AWG GREEN GROUND INSULATED CONDUCTOR
6 FT
M6 x 1.0 x 20 MM LONG STAINLESS STEEL HEX BOLT
4
M6 STAINLESS STEEL LOCKWASHER
4
M6 STAINLESS STEEL FLATWASHER
4
6 AWG TO 2 AWG C-TAP CU
2
2 HOLE COMPRESSION LUG 6 AWG CU .75 CENTER TO CENTER
2
3/4” METAL CLAMP
6
CONNECTOR 1
HEYCO
P/N
3214
ALARM CABLE, SOLID #24 AWG, DB 9, 20 FT.
1
Note
1. Interconnection hardware between the UPS and service entrance is not included in this kit.
2. All conductors are stranded, copper, unless noted.