Online power, Torque value – OnLine Power Telecommunication User Manual
Page 10

i
OnLine Power
TORQUE VALUE
TERMINAL or BOLT
TORQUE
IN/LBS. N-METER
DEAD FRONT PANEL
49.60
5.61
TB1 18.0
2.03
TB2 18.0
2.03
ELECTRONIC TRAY GROUND
14.16
1.6
TRAY TO CABINET SCREW
49.6
5.61
CIRCUIT BREAKER, TERMINALS 27.0
3.0
SURGE PROTECTOR
25.48
2.88
CONDUIT INLET COVER PLATE
OVER TORQUE WILL DAMAGE THE GASKET
18.24 2.08
BATTERY CONNECTIONS
68.17
7.7
DOOR GND
49.60
5.61
GROUND LUGS, ON OUTSIDE
49.60
5.61
PAD MOUNTING BRACKET
84.96
9.6
This unit was designed for specific applications. It should not be modified and/or used for any application
other than for that which it was designed. Optional equipment not described in the sales literature or this
manual should not be installed without first checking with the Service department. If you have any
questions about this unit’s application call the Service department at the number shown on the page f.