Online power – OnLine Power Telecommunication User Manual
Page 37

OnLine Power
3-7
REV A
23
22
21
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
G
(-)
(+)
DOOR
SWITCH
INPUT
POWER
INPUT
HEATER
VOLTAGE
CB7
CB6
OUTPUT POWER
CB5
CB4
G
N
L
G
N
L
G
N
L
G
N
L
G
N
L
G
N
L
TO ADJUNCT BATTERY CABINET
CONNECTIONS AT TB1 OF MAIN UPS CABINET
ILLUSTRATION 3-3
TB1-1
INPUT VOLTAGE - HOT LINE
TB1-2
INPUT VOLTAGE - NEUTRAL FOR 120V, LOW LINE FOR OTHER VOLTAGES
TB1-3 INPUT
GND
TB1-4
OUTPUT #1 - HOT LINE
TB1-5
OUTPUT #1 - NEUTRAL FOR 120V, LOW LINE FOR OTHER VOLTAGES
TB1-6
OUTPUT #1 - GND
TB1-7
OUTPUT #2- HOT LINE
TB1-8
OUTPUT #2 - NEUTRAL FOR 120V, LOW LINE FOR OTHER VOLTAGES
TB1-9
OUTPUT #2 - GND
TB1-10
OUTPUT #3- HOT LINE
TB1-11
OUTPUT #3 - NEUTRAL FOR 120V, LOW LINE FOR OTHER VOLTAGES
TB1-12
OUTPUT #3 - GND
TB1-13
OUTPUT #4- HOT LINE
TB1-14
OUTPUT #4 - NEUTRAL FOR 120V, LOW LINE FOR OTHER VOLTAGES
TB1-15
OUTPUT #4 - GND
TB1-16
HEATER VOLTAGE - HOT LINE FOR OPTIONAL ADJUNCT BATTERY CABINET
TB1-17
HEATER VOLTAGE - NEUTRAL FOR 120V, LOW LINE FOR OTHER VOLTAGES. ROUTE
WITH TB1-16
TB1-18
GND. ROUTE WITH TB1-16
TB1-19
DOOR SWITCH (N/O) FROM OPTIONAL ADJUNCT BATTERY CABINET
TB1-20
DOOR SWITCH (N/O) RTN FROM OPTIONAL ADJUNCT BATTERY CABINET
TB1-21
+96VDC FROM OPTIONAL ADJUNCT BATTERY CABINET
TB1-22
-96VDC FROM OPTIONAL ADJUNCT BATTERY CABINET
TB1-23
GND FROM OPTIONAL ADJUNCT BATTERY CABINET