3-5 LIFTING
REQUIREMENTS
•
See Illustration 3-1 for location of two eyebolts and lifting details.
•
Use Load - Rated Snaps on end of chain and a Spreader Bar.
CAUTION
WARNING!
• Because the PBC-II Cabinets and it’s contents, (batteries) are extremely heavy, the use of Power
Equipment is necessary.
•
Total weight for 1600W PBC Model is 899 lbs.
•
Electronic Tray weight is approximately 55 lbs.
•
The Battery weight, with a set of 8 batteries, is approximately 656 lbs.
•
Power Backup Cabinet enclosure weight is approximately is 203 lbs.
•
Pole mount adapter plates with hardware is approximately 10 lbs.
•
Verify that the two eyebolts are secured and screwed at the top of the cabinet by turning it clockwise till
tight. Two eyebolts with rubber washers are supplied in a bag inside the cabinet.
•
Unit may be lifted using two eyebolts, located at the top roof of cabinet.
3-6 PBC-II
POLE
INSTALLATION
CAUTION
a) A service disconnect switch having overcurrent protection is to be connected between
the UPS and the utility transformer.
b) A bucket truck and other suitable equipment, including climbing spikes and safety
harness are to be used during installation or servicing of the UPS on the utility pole.
c) The utility power conductors are to be connected to this UPS through an appropriate
service entrance weather head.
d) Permission to mount the UPS on the utility pole shall be in accordance with agreements
between the cable company and the utility company.
• With the successful completion of the unpacking of the PBC-II, proceed to next step, which is the
mounting of the unit to the pole.