Troubleshooting | 74
SAM-e
Symptom
Cause
Corrective Action(s)
SAM-e spitting out water
1 “P” Trap too close to SAM-e
1 “P” trap must be at least 12 in (30
cm) below header. Relocate if
required.
2 Condensate line not sloped
sufficiently
2 Ensure line is sloped sufficiently to
carry condensate produced.
3 Steam line not insulated
3 If steam line is long condensate build
up could overload the SAM-e
condensate port. Insulate the steam
line to improve efficiency and install
condensate traps as required.
SAM-e Grommet leaks
1 Distributor tubes not seated
properly
1 Push distributor tubes down until
support washer is resting on rubber
grommet.
2 Grommet Damaged
2 Replace any damaged grommets
Blower Pack
Symptom
Cause
Corrective Action(s)
Blower not operating
Note: Blower pack does not
come on unless steam is
being produced by the
humidifier.
1 No power to blower pack
1a Check power connection.
1b Check blower pack fuses
2 On/Off Thermostat not closing
2 Check wiring to thermostat replace if
it does not close when it is exposed to
steam.
Digital Humidistat
Symptom
Cause
Corrective Action(s)
Humidistat Reading incorrectly
1 Sensor out of calibration
1 See humidistat manual.
2 Improper sensor location
2 Check that the humidistat is
positioned in a location
representative of room humidity.
3 Exposed to draft or heat source
3 Check that heat/cold fluctuations,
drafts, sunlight, doors, or vents are
affecting the reading.
4 No vapour barrier
4 Ensure drafts cannot affect reading
by ensuing vapour barrier is in place
and working.