Page 27
Installation | 24
On/Off Control Wiring
Figure 15: On/Off Controls
Figure 16: Digital On/Off Humidistat
Note: 1
2
3
4
Humidifier will run when circuit between
terminal 1 and 2 on humidifier is closed.
Terminal 1 is 24 VAC Hot, turn unit off to
avoid shorting while wiring.
Digital Humidistat requires 24 VAC power
from terminals 1 and 3 of humidifier.
2520273 - Digital On/Off Duct Humidistat
can also be used for duct high limit. Wire
in series to 3 - Common and 4 - Digital Out
of the humidistat.
Humidifier Terminal Strip
Air Proving
Switch
Duct High