beautypg.com

On/off control wiring, Installation | 24, Figure 15: on/off controls – Nortec NH-EL Series User Manual

Page 27

background image

Installation | 24

On/Off Control Wiring
















Figure 15: On/Off Controls



Figure 16: Digital On/Off Humidistat

Note: 1

2

3

4

Humidifier will run when circuit between

terminal 1 and 2 on humidifier is closed.
Terminal 1 is 24 VAC Hot, turn unit off to
avoid shorting while wiring.
Digital Humidistat requires 24 VAC power
from terminals 1 and 3 of humidifier.

2520273 - Digital On/Off Duct Humidistat

can also be used for duct high limit. Wire
in series to 3 - Common and 4 - Digital Out
of the humidistat.

Humidifier Terminal Strip

Air Proving

Switch

Duct High

Limit

2548731 - Digital

On/Off Humidistat

1

C

om

m

on

2

24

VA

C

3

D

ig

ita

l I

n

4

D

ig

ita

l O

ut

5

F

an

Acti

va

tion

6

F

an

Acti

va

tion

7

Te

m

pe

ra

tu

re

8

Te

m

pe

ra

tu

re