beautypg.com

Steam distributor – Nortec NH-EL Series User Manual

Page 18

background image

15 | Installation

Steam Distributor

Steam generated by the NH-EL may be distributed directly into a space with a built on or

remote blower pack, or into an air handling system using either Nortec steam distributors or
Nortec’s SAMe steam distribution manifold.

Whichever method is used, the steam distributor should be installed as close as possible to

the humidifier. Short steam distribution lines minimize condensate losses and the possibility
of generating back pressure in the steam distribution line.

Figure 8: Distributor Location in Duct provides common guidelines for locating a steam

distributor in a duct.







Figure 8: Distributor Location in Duct



12 in.

(30 cm)

min.

Calculated absorption

distance to any obstruction

or 8-10 ft (2.4 - 3 m)

if unknown

Mount distributor

to side of duct

2 x duct

height min.

2/3 Duct
height

Note:

Install the NH-EL as close as possible to whatever steam distributor is used.

Refer to distributor, SAMe, or remote blower pack installation manuals for detailed installation

instructions.