Steam distributor – Nortec NH-EL Series User Manual
Page 18
15 | Installation
Steam Distributor
Steam generated by the NH-EL may be distributed directly into a space with a built on or
remote blower pack, or into an air handling system using either Nortec steam distributors or
Nortec’s SAMe steam distribution manifold.
Whichever method is used, the steam distributor should be installed as close as possible to
the humidifier. Short steam distribution lines minimize condensate losses and the possibility
of generating back pressure in the steam distribution line.
Figure 8: Distributor Location in Duct provides common guidelines for locating a steam
distributor in a duct.
Figure 8: Distributor Location in Duct
12 in.
(30 cm)
min.
Calculated absorption
distance to any obstruction
or 8-10 ft (2.4 - 3 m)
if unknown
Mount distributor
to side of duct
2 x duct
height min.
2/3 Duct
height
Note:
Install the NH-EL as close as possible to whatever steam distributor is used.
Refer to distributor, SAMe, or remote blower pack installation manuals for detailed installation
instructions.