Installation | 32
Outdoor Temperature Setback Sensor
Figure 29: Outdoor Temperature Reset
Each digital controller is equipped with an integrated reset function that can reduce the
setpoint during cold weather operation. This will prevent condensation on windows and
building structures. The above graph illustrates how the setpoint reset feature operates.
This feature is enabled by removing the jumper from terminals 8 and 1 on the humidistat
and wiring the outdoor temperature sensor to these terminals.
When the outdoor temperature setback feature is in effect, the humidistat will normally
display the calculated setpoint limit based on the outdoor air temperature. A snowflake will
also be displayed to indicate cold weather operation. When any key on the controller is
pressed, the LCD screen will display the customer specified setpoint for a short duration.
Figure 30: Outdoor Temperature Sensor
SE
TP
O
IN
T
LI
MI
T
(%R
H
)
OUTDOOR TEMPERATURE
1 – 24 VAC
2 – On/Off Loop
3 – Common
4 – Channel 1
5 – Channel 2
6 – 10 VDC
7 – Ground
8 – Blower Pack
9 – Blower Pack