55 | Maintenance and Servicing

Configuration Submenu

The configuration submenu provides access to most user configurable settings. It is further
broken down into Features, Control Settings, General, and Comms. submenus. Select any
submenu by touching it on the screen.



Figure 45: Configuration Submenu

Features Submenu

Drain Cool
When On the fill valve is activated at any time that the drain valve is
activated to cool the drain water. (Default = On).
Idle Mode
Configures operation when no demand is present. Idle Only = no action.
Idle Drain = drain cylinder after Idle Drain Time. Keep Warm = keep
cylinder warm by periodically engaging contactor. (Default = Idle Drain).
Idle Drain Time
When Idle Mode = Idle Drain configures time the humidifier waits with no
demand before the cylinder is drained. (Default = 72 hours).
3DD Force
When On the humidifier will drain the contents of the cylinder every 3 days
regardless of demand or idle condition. It can improve performance for
water conditions with sediment or other contaminants. (Default = Off).

Dfactor
Increases or decreases the drain time used to control cylinder water conductivity. It should not
normally need to be adjusted. A NORTEC representative will provide instructions if it should
need to be adjusted. (Default = 1.0).
Drain Mode
Configures when a corrective drain will be performed in case the software detects excess
current. Fixed ED = drain at 115% of full capacity. Float ED = drain at 115% of current
demand. (Default = Fixed ED).
Foam Mode
These settings can be used to detect foaming in the cylinder and take corrective action. Basic
is a software only setting. Advanced requires installation of a hardware kit. (Default = Off,
Default with Kit = Advanced).
Cal. Drain Mode
Sets how the humidifier drains to control cylinder water conductivity. Basic = normal drain,
Prefill = fill then drain, Multi = fill then drain to trigger point until drain duration elapsed. (Default
= Basic).