Use appropriate slope insulate pipe – Nortec NH-EL Series User Manual
Page 20
17 | Installation
Steam Direction
Steam Direction
Steam
Directio
n
2 in.
(5 cm)
1 ft (30 cm)
1ft (30 cm)
0.5 in.
(12 mm)
10 Degrees
2 Degrees
Use Appropriate Slope
Insulate Pipe
1 in. (2.5 cm) pipe
insulation
Minimal Slope (up)
Minimal Slope (down)
Figure 10: Condensate Traps
Figure 9: Steam Line Slope and Insulation
Trap condensate
Trap at all low points and recommended intervals using full size ‘T’ for traps.
Condensate should not be routed to a sink used frequently by personnel. Route to a floor
drain or equivalent. Condensate normally cools in traps but is still hot. A SAMe or larger
steam line generates more condensate and water may not cool in the trap. A drain water
cooler option may be installed if required by code.
Route condensate to floor drain or equivalent in multi-unit to single SAM-e installation.
12 in. (30 cm)
min drop to
top of ‘P’ Trap
P Trap min
6 in. (15 cm)
or
duct static
pressure + 2 in
whichever is
greater
Tee is same size
as steam line
Use a full size tee, not a 90
degree elbow for vertical
to horizontal transitions.
‘P’ Traps Use:
- NORTEC 0.375 in condensate hose
- 1/4 in Med-L copper tubing, or
- 0.375 in stainless steel tubing
Condensate drains must be sloped down.
1 ft (30 cm)
0.25 in
(0.6 cm)