Never, Install a valve or other obstruction – Nortec NH-EL Series User Manual
Page 23
Installation | 20
8. Increase diameter either on down slope or install condensate trap.
9. Install condensate traps if steam line > 15 ft (4.5 m).
10. In addition never:
Best
Good
Never
Nortec
Condensate
Trap
Sloping Down
Increase =
Condensate
Blockage
Best
Good
Never
Nortec
Condensate
Trap
Sloping Down
Increase =
Condensate
Blockage
max. 15 ft
(4.5 m)
max. 15 ft
(4.5 m)
Good
Never
> 15 ft
(4.5 m)
max. 15 ft
(4.5 m)
max. 15 ft
(4.5 m)
Good
Never
> 15 ft
(4.5 m)
Never
Install a valve or other obstruction
Never
Never
Reduce Steam Line Size
Install Copper or SST without Insulation
Never
Install a valve or other obstruction
Never
Never
Reduce Steam Line Size
Install Copper or SST without Insulation
Never
Install a valve or other obstruction
Never
Never
Reduce Steam Line Size
Install Copper or SST without Insulation
Never
Install a valve or other obstruction
Never
Never
Reduce Steam Line Size
Install Copper or SST without Insulation
Never
Install a valve or other obstruction
Never
Never
Reduce Steam Line Size
Install Copper or SST without Insulation
After Installation Always:
Purge steam lines to remove any contaminants and installation materials
Ensure all condensate lines / traps flow.