11 | Installation
6 in.
(15 cm)
Recommended
Side
Clearance
36 in. (91.5 cm)
Min. Front Clearance
24 in.(61 cm)
Min Height
Mount Humidifier
Level
5-95%
(See Table for
Blowerpack
clearances)
(See Table for
Blowerpack
clearances)
(See Table for
Blowerpack
clearances)
If Blowerpack is used,
mount so that the steam
outlet is at least
96 in. (244 cm)
above ground level.
Location
Mount on a suitable wall or vertical surface. Do not sit the unit on the floor to allow
clearances required for plumbing and electrical connections.
Clearance dimensions shown are for reference only and are the minimum required for
maintenance of the humidifier. Consult local and national codes before final location and
installation. NORTEC does not accept responsibility for installation code violations.
Install only in areas with ambient temperature 41-104 °F (5 – 40 °C) relative humidity 5 -
95% (non condensing).
When possible install the humidifier below the steam distributor. Take care to provide proper
steam line routing and proper condensate traps.
DO NOT locate the humidifier any further than absolutely necessary from the steam
distributor location. Net output will be reduced as a result of heat loss through the steam
line.
When possible, mount the NH-EL humidifier at a height convenient for servicing.
Figure 5: Mounting Location / Clearance
Note: Do not mount on hot surfaces, where freezing can occur, vibrating surface, or
floor.